Encoder 3: Coarse Position Error; Encoder 3: Internal Power Supply Voltage Faulty; Encoder 3: Signal Level A/B Unipolar Outside Tolerance - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

SINAMICS alarms
Note:
If the encoder cables 6FX2002-2EQ00-.... and 6FX2002-2CH00-.... are interchanged, this can result in the encoder
being destroyed because the pins of the operating voltage are reversed.
Remedy:
Re fault value, bit 0 = 1:
- correct encoder cable connected?
- check the plug connections of the encoder cable.
- SMC30: Check the parameterization (p0404.22).
Re fault value, bit 1 = 1:
- correct encoder cable connected?
- replace the encoder or encoder cable
Re fault value, bit 2 = 1:
- correct encoder cable connected?
- replace the encoder or encoder cable
Re fault value, bit 3 = 1:
- correct encoder cable connected?
- replace the encoder or encoder cable
233121
<location>Encoder 3: Coarse position error
Message value:
-
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF1 (NONE, OFF2, OFF3)
Acknowledge:
PULSE INHIBIT
Cause:
For the actual value sensing, an error was detected on the module. As a result of this error, it must be assumed that
the actual value sensing supplies an incorrect coarse position.
Remedy:
Replace the motor with DRIVE-CLiQ or the appropriate Sensor Module.
233122
<location>Encoder 3: Internal power supply voltage faulty
Message value:
%1
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
ENCODER
Acknowledge:
IMMEDIATELY
Cause:
Fault in internal reference voltage of ASICs for encoder 3.
Fault value (r0949, interpret decimal):
1: Reference voltage error.
2: Internal undervoltage.
3: Internal overvoltage.
Remedy:
Replace the motor with DRIVE-CLiQ or the appropriate Sensor Module.
233123
<location>Encoder 3: Signal level A/B unipolar outside tolerance
Message value:
Fault cause: %1 bin
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF1 (IASC/DCBRAKE, NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The unipolar level (AP/AN or BP/BN) for encoder 3 is outside the permissible tolerance.
Fault value (r0949, interpret binary):
Bit 0 = 1: Either AP or AN outside the tolerance.
Bit 16 = 1: Either BP or BN outside the tolerance.
The unipolar nominal signal level of the encoder must lie in the range 2500 mV +/- 500 mV.
The response thresholds are < 1700 mV and > 3300 mV.
810
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0