Profibus/Profinet: Configuration Of Dp Master Bus %1 Has Been Changed; Profibus/Profinet: Bus %3, Configuration Error %1, Parameter %2 - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

611D drive alarms
SDB source:
- 99 = Passive file system: _N_SDB_DIR
- 100 = CF card: /siemens/sinumerik/sdb/...
- 101 = CF card: /addon/sinumerik/sdb/...
- 102 = CF card: /oem/sinumerik/sdb/...
- 103 = CF card: /user/sinumerik/sdb/...
Reaction: PROFIBUS/PROFINET is inactive or working with the default SDB.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
- Check the setting of MD 11240 $MN_PROFIBUS_SDB_NUMBER.
- If source = 100: Check directory _N_SDB_DIR in the passive file system.
- If source = 103-106: Check directories on CF card
Program
Switch control OFF - ON.
Continuation:
380022

PROFIBUS/PROFINET: Configuration of DP master bus %1 has been changed

Parameters:
%1 = Number of the affected bus
Definitions:
The PROFIBUS configuration on the DP master was changed during operation, e.g. by downloading a new hardware
configuration via STEP 7. As the cycle data may also have changed, operation cannot be continued, and a warm start
is required.
If the master functionality is within the PLC (as on the 840Di), the PLC will have been stopped for the download, and
alarm 2000 (PLC sign-of-life) output.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
NCK restart
If the error cannot be eliminated by this procedure, please make a note of the error text and contact the control system
manufacturer.
Program
Switch control OFF - ON.
Continuation:
380040

PROFIBUS/PROFINET: Bus %3, configuration error %1, parameter %2

Parameters:
%1 = Cause of the error
%2 = Parameter
%3 = Number of the affected bus
Definitions:
The generation of the PROFIBUS/PROFINET in the SDB does not conform to the configuration specifications of the
NC in use.
Overview: Cause of the error, par 1:
- 01 = SDB contains slave/device without diagnostics slot, slave/device address
- 02 = SDB contains too many slot entries, identifier
- 03 = SDB contains no equidistance data, no function
- 04 = PNIO: SDB contains different Tdp (also TDC) on one device
- 05 = PNIO: SDB contains different Tmapc (also CACF) on one device
- 06 = PNIO: SDB contains different TI on one device
- 07 = PNIO: SDB contains different TO on one device
- 08 = PNIO: SDB contains device numbers that are too high (with values higher than 126)
- 09 = SDB content transferred segmented (too many slots/frames)
- 10 = Not enough memory space for segmented SDB content (too many slots/frames)
896
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0