SINAMICS alarms
201006
<location>Firmware update for DRIVE-CLiQ component required
Message value:
Component number: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The firmware of a DRIVE-CLiQ component must be updated as there is no suitable firmware or firmware version in
the component for operation with the Control Unit.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Firmware update using the commissioning software:
The firmware version of all of the components on the "Version overview" page can be read in the Project Navigator
under "Configuration" of the associated drive unit and an appropriate firmware update can be carried out.
Firmware update via parameter:
- take the component number from the alarm value and enter into p7828.
- start the firmware download with p7829 = 1.
201007
<location>POWER ON for DRIVE-CLiQ component required
Message value:
Component number: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A DRIVE-CLiQ component must be powered up again (POWER ON) as, for example, the firmware was updated.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Note:
For a component number = 1, a POWER ON of the Control Unit is required.
Remedy:
Switch off the power supply of the specified DRIVE-CLiQ component and switch it on again.
201009
<location>CU: Control module overtemperature
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r0037[0]) of the control module (Control Unit) has exceeded the specified limit value.
Remedy:
- check the air intake for the Control Unit.
- check the fan for the Control Unit (only for CU310).
Note:
The alarm automatically disappears after the limit value has been undershot.