Tm: Temperature Alarm Threshold Channel 4 Exceeded; Hw Problem With The Tm Module; Drive-Cliq Component Does Not Support Function - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

235214
<location>TM: Temperature alarm threshold channel 4 exceeded
Message value:
%1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828, TM120
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature measured using the temperature sensing of the Terminal Module 120 (TM120) (r4105[3]) has
exceeded the threshold value to initiate this alarm (p4102[6]).
For PTC, the following applies:
- if r4101[3] > 1650 ohms, the temperature r4105[3] = 250 °C
- if r4101[3] <= 1650 ohms, the temperature r4105[3] = -50°C
Alarm value (r2124, interpret decimal):
Temperature value multiplied by 10 at the point of initiation.
Remedy:
See also: p4102 (TM120 temperature evaluation fault/alarm threshold)
235230
<location>HW problem with the TM module
Message value:
%1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828, TM120
Reaction:
Servo: NONE
Infeed: OFF1 (NONE, OFF2)
Acknowledge:
POWER ON
Cause:
The Terminal Module (TM) used has signaled internal errors.
Signals from this module may not be evaluated because they are very likely to be incorrect.
Remedy:
If required, replace the Terminal Module.
235233
<location>DRIVE-CLiQ component does not support function
Message value:
%1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828, TM120
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A function requested by the Control Unit is not supported by a DRIVE-CLiQ component.
Fault value (r0949, interpret decimal):
1: Terminal Module 31 does not support the function "Timer for temperature evaluation" (X522.7/8, p4103 > 0.000).
Remedy:
Re fault value = 1:
- De-activate timer for temperature evaluation (X522.7/8) (p4103 = 0.000).
- Use Terminal Module 31 and the relevant firmware version to enable the "Timer for temperature evaluation" function
(Order No. 6SL3055-0AA00-3AA1, firmware version 2.6 and higher).
See also: p4103 (TM120 temperature evaluation timer)