No Output Slot Available For Basic Address %1 (Size %2); Output Slot For Basic Address %1 (Size %2) Not Allowed - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Remedy:
Enter correct base addresses in the machine data:
- For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTIN.
- For length=2: Correct machine data MN_HW_ASSIGN_ANA_FASTIN.
- NCK restart
If the error cannot be eliminated by this procedure, please make a note of the error text and contact the control system
manufacturer.
Program
Switch control OFF - ON.
Continuation:
380071
PROFIBUS/PROFINET: No output slot available for basic address %1 (size %2)
Parameters:
%1 = Logical base address of the requested area
%2 = Size of the area in bytes
Definitions:
An incorrect logical base address was specified for a digital or analog input. Either no slot has been configured for this
base address or the requested area extends beyond the end of the slot.
For length =1 it is a digital output,
For length =2 it is an analog output.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Enter correct base addresses in the machine data:
- For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTOUT.
- For length=2: Correct machine data MN_HW_ASSIGN_ANA_FASTOUT.
- NCK restart
If the error cannot be eliminated by this procedure, please make a note of the error text and contact the control system
manufacturer.
Program
Switch control OFF - ON.
Continuation:
380072
PROFIBUS/PROFINET: Output slot for basic address %1 (size %2) not allowed
Parameters:
%1 = Logical base address of the requested area
%2 = Size of the area in bytes
Definitions:
An incorrect logical base address was set for a digital or analog output, the area is resides in the access range of the
PLC (PIQ, base addresses < 256).
For length =1 it is a digital output,
For length =2 it is an analog output.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Only use addresses outside the PLC process image (e.g. >= 256) for output slots.
Enter correct basic addresses in the machine data:
- For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTOUT.
- For length=2: Correct machine data MN_HW_ASSIGN_ANA_FASTOUT.
- NCK restart
If the error cannot be eliminated by this procedure, please make a note of the error text and contact the control system
manufacturer.
Program
Switch control OFF - ON.
Continuation:
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
611D drive alarms
899