10655
[Channel %1: ] Synchronization of gantry group %2 in progress
Parameters:
%1 = Channel number
%2 = Gantry unit
Definitions:
The alarm may be suppressed with MD37150 $MA_GANTRY_FUNCTION_MASK Bit2 = 1.
Reaction:
Alarm display.
Remedy:
--
Program
Alarm display showing cause of alarm disappears. No further operator action necessary.
Continuation:
10656
[Channel %1: ] Axis %2 gantry slave axis dynamically overloaded
Parameters:
%1 = Channel number
%2 = Axis
Definitions:
The indicated gantry slave axis is dynamically overloaded, i.e. the slave axis cannot follow the master axis dynamically
Reaction:
Mode group not ready.
Local alarm reaction.
Channel not ready.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. Compare the axial machine data of the gantry slave axis
with the data of the gantry master axis
Program
Teileprogramm neu starten.Clear alarm with the RESET key in all channels of this mode group. Restart part program.
Continuation:
10657
[Channel %1: ] Axis %2 power OFF in the gantry error limit exceeded status
Parameters:
%1 = Channel number
%2 = Axis
Definitions:
Gantry error limit exceeded status (alarm 10653) has been switched off.
The error can only be removed by deleting MD37135 $MA_GANTRY_ACT_POS_TOL_ERROR or by
deactivating the extended monitoring (MD37150 $MA_GANTRY_FUNCTION_MASK Bit0).
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Please inform the authorized personnel/service department.
1. Remove a mechanical misalignment
2. Check axis (uneven mechanical movement?)
3. Delete MD37135 $MA_GANTRY_ACT_POS_TOL_ERROR or deactivate the extended monitoring
4. MD37120 $MA_GANTRY_POS_TOL_ERROR is set incorrectly
If the MD is changed, a Power ON will be required.
Program
Clear alarm with the RESET key. Restart part program
Continuation: