201150
<location>CU: Number of instances of a drive object type exceeded
Message value:
Drive object type: %1, number permitted: %2, actual number: %3
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The maximum permissible number of instances of a drive object type was exceeded.
Fault value (r0949, interpret hexadecimal):
Byte 1: Drive object type (p0107).
Byte 2: Max. permissible number of instances for this drive object type.
Byte 3: Actual number of instances for this drive object type.
Remedy:
- power down the unit.
- suitably restrict the number of instances of a drive object type by reducing the number of inserted components.
- re-commission the unit.
201151
<location>CU: Number of drive objects of a category exceeded
Message value:
Drive object category: %1, number permitted: %2, actual number: %3
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The maximum permissible number of drive objects of a category was exceeded.
Fault value (r0949, interpret hexadecimal):
Byte 1: Drive object category.
Byte 2: Max. permissible number for this drive object category.
Byte 3: Actual number for this drive object category.
Remedy:
- power down the unit.
- suitably restrict the number of drive objects of the specified category by reducing the number of inserted components.
- re-commission the unit.
201200
<location>CU: Time slice management internal software error
Message value:
%1
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A time slice management error has occurred.
It is possible that the sampling times have been inadmissibly set.
Fault value (r0949, interpret hexadecimal):
998: Too many time slices occupied by OA (e.g. DCC)
999: Too many time slices occupied by the basic system
Too many different sampling times may have been set.
Further values for internal Siemens troubleshooting.
Remedy:
- check the sampling time setting (p0112, p0115, p4099).
- contact the Hotline.