Fpga Data Faulty; Power Unit: Undervoltage When Opening The Brake; Pre-Charge Contactor Monitoring - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Cause:
EEPROM data error of the power unit module.
Fault value (r0949, interpret hexadecimal):
0: The EEPROM data read in from the power unit module is inconsistent.
1: EEPROM data is not compatible to the firmware of the power unit application.
Additional values:
Only for internal Siemens troubleshooting.
Remedy:
Re fault value = 0:
Replace the power unit module or update the EEPROM data.
Re fault value = 1:
The following applies for CU31x and CUA31:
Update the firmware \SIEMENS\SINAMICS\CODE\SAC\cu31xi.ufw (cua31.ufw)
230053
<location>FPGA data faulty
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
Power unit module FPGA data error.
Remedy:
Replace the power unit module or update the FPGA data.
230054
<location>Power unit: Undervoltage when opening the brake
Message value:
%1
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
NONE
Acknowledge:
NONE
Cause:
When the brake is being opened, it is detected that the 24 V supply voltage is less than 24 V - 10 % = 21.6 V.
Alarm value (r2124, interpret decimal):
Supply voltage fault [resolution = 0.1 V].
Example:
Alarm value = 212 --> voltage = 21.2 V
Remedy:
Check the 24 V supply voltage to the power unit.
230060
<location>Pre-charge contactor monitoring
Message value:
Fault cause: %1 bin
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
At the end of the monitoring time (p0255[0]), the actual state of the pre-charge contactor does not match the desired
state.
Bit 0: Monitoring time exceeded.
Bit 1: Contactor opened during operation.
Bit 2: Contactor closed in OFF state.
Remedy:
- check the monitoring time setting p0255[0].
- check the contactor wiring and activation.
- replace the contactor.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
705