[Channel %1:] Block %3 Axis %2 Working Area Limitation %4; Block %5 Axis %2 Working Area Limitation Violated - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

NCK alarms
Remedy:
a) Check NC program for correct positional data and, if necessary, make corrections.
b) Check zero offsets (current frame)
c) Correct working area limitation via G25/G26, or
d) Correct working area limitation via setting data, or
e) Deactivate working area limitation via setting data 43410 WORKAREA_MINUS_ENABLE=FALSE
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
10731
[Channel %1: ] Block %3 axis %2 working area limitation %4
Parameters:
%1 = Channel number
%2 = Axis name, spindle number
%3 = Block number, label
%4 = String ( + or - )
Definitions:
The motion planned for the axis violates the currently active working area limit.
The alarm is activated during the preparation of approach or rest blocks for REPOS.
This alarm is issued instead of alarm10733 if bit11 is not set in MD11411 $MN_ENABLE_ALARM_MASK.
Reaction:
Local alarm reaction.
Interface signals are set.
Alarm display.
Remedy:
Determine the cause of the offset from the initial or target position. The REPOS command is executed at the end of
an ASUB or system ASUB. See also cross reference from ASUBs.
Check the currently active work offset via the current frame.
Also check the external work offsets, overlaid movements ($AA_OFF), DRF and transformation components.
Cancel NC program with NC reset.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
10732
[Channel %1: ] Block %5 axis %2 working area limitation violated, residual distance:
%6 %3<ALUN>
Parameters:
%1 = Channel number
%2 = Axis name, spindle number
%3 = Unit of distance
%4 = Block number, label|residual distance
Definitions:
This alarm is generated if it is determined during block preprocessing that the programmed path of the stated axis vio-
lates the working area limitation.
If MD11411 $MN_ENABLE_ALARM_MASK, bit11=1, this alarm is issued instead of alarm 10730. Alarm 10732 offers
an expanded diagnostics option for the working area limitation violation. The condition for activation is the presence
of the ALUN* alarm file in the HMI.
Reaction:
Correction block is reorganized.
Local alarm reaction.
Interface signals are set.
Alarm display.
Remedy:
a) Check NC program for correct positional data and, if necessary, make corrections.
b) Check zero offsets (current frame)
c) Correct working area limitation via G25/G26, or
d) Correct working area limitation via setting data, or
e) Deactivate working area limitation via SD43410 $SA_WORKAREA_MINUS_ENABLE=FALSE
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
86
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms