<location>IF1: PB/PN clock cycle signal error when establishing bus communication
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The bus is in the data exchange state and clock synchronous operation has been selected using the parameterizing
telegram. The global control telegram for synchronization is being irregularly received.
-.the master is sending an irregular global control telegram.
- the master is using another clock synchronous DP clock cycle than was transferred to the slave in the parameterizing
telegram.
Remedy:
- check the master application and bus configuration.
- check the consistency between the clock cycle input when configuring the slave and clock cycle setting at the master.
Note:
IF1: Interface 1
PB: PROFIBUS
PN: PROFINET
201944
<location>IF1: PB/PN sign-of-life synchronism not reached
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The bus is in the data exchange state and clock synchronous operation has been selected using the parameterizing
telegram. Synchronization with the master sign-of-life (STW2.12 ... STW2.15) could not be completed because the
sign-of-life is changing differently to how it was configured in the Tmapc time grid.
Remedy:
- ensure that the master correctly increments the sign-of-life in the master application clock cycle Tmapc.
- correct the interconnection of the master sign-of-life (p2045).
Note:
IF1: Interface 1
PB: PROFIBUS
PN: PROFINET
201950
<location>IF1: PB/PN clock cycle synchronous operation synchronization
unsuccessful
Message value:
-
Drive object:
All objects
Reaction:
OFF1 (NONE)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Synchronization of the internal clock cycle to the global control telegram has failed. The internal clock cycle exhibits
an unexpected shift.
Remedy:
Only for internal Siemens troubleshooting.
Note:
IF1: Interface 1
PB: PROFIBUS
PN: PROFINET
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
599