6.8
Interlink Transmission Parameters
Set the link device transfer range between network modules. (
● Up to 64 link device transfer range settings are available for each link of network modules.
● When setting of 65 or more link device transfer ranges is required, use link direct devices in the sequence program to
perform the link transfer.
1.
Configure the network setting. (
2.
Open the "Setting the CC IE/MELSECNET Interlink Transmission Parameters" window in the
programming tool.
Project window
3.
From the selection tree, select the source and target modules to set interlink transmission
parameters for them.
4.
Configure settings with reference to the description below.
5.
Click the
232
Page 180, Section 6.2)
[Parameter]
[Network Parameter]
button
button.
Page 89, Section 4.1.11)
[Ethernet/CC IE/MELSECNET]