Transient Transmission Is Disabled - Mitsubishi Electric MELSEC Q Series Reference Manual

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

10.1.7

Transient transmission is disabled

The following flowchart shows the procedures to be taken when transient transmission is disabled.
Transient transmission is disabled.
Is D LINK LED of own or
another station ON or flashing?
Station No. setting status
(own station) (SB0070)
Baton pass status of each station
(SW00A0 to SW00A7)
What is control data completion status?
Are Target station's CPU type,
Target network No. and Target station No.
in control data correct?
Execute a communication test using the programming tool.
Page 174, Section 5.7.1
Check the sequence program of other stations
(for overwriting of data).
504
ON/flashing
OFF (Station No. set)
Relevant bit OFF
(Normal baton pass station)
"0"
Correct
Test result?
Completed normally
End
OFF
Page 500, Section 10.1.4
ON
(Station No.
not set)
Using the UINI instruction, set station No.
Page 476, Section 9.18
Relevant bit ON
(Baton pass
error station)
Connect the programming tool to another station.
Check error factors in the CC IE Control
diagnostics, and take corrective actions according
to the troubleshooting section.
Page 541, Section 10.4
"Other
Check the error details by the error code and take
than 0"
corrective actions.
Page 511, Section 10.2
Incorrect
Modify the control data.
Page 324, CHAPTER 9
Failed
Modify routing parameters.
Page 238, Section 6.9