(1) Setting network parameters
Set the same network No. to multiple CC-Link IE Controller Network modules in the network setting.
The setting is explained using the following system configuration, where two CC-Link IE Controller Network
modules are mounted.
The setting example indicates
this part of the configuration.
Control station
1M
1
P
(a) Network setting
Configure the network setting as shown below.
(b) Network range assignment
Set each station's send range in LB/LW in "LB/LW Setting" of "Network Range Assignment" of the control
station. (
Page 185, Section 6.3.1)
Normal station
1N
2
Normal station
S
1N
3
S
CHAPTER 4 FUNCTIONS
Normal station
Normal station
1N
4
1N
5
S
S
Set one station as the control station.
Multiple control stations cannot be configured.
Set the same network No.
Set a unique station number for each station.
The same station No. cannot be set to
multiple stations.