(2) Using equal assignment
The link device I/O range can be equally assigned between the I/O master and other stations. (LX/LY Setting(1)
only)
1.
Open the "Assignment the CC IE Control Network Range" window in the programming tool.
(
2.
Click the
3.
Configure settings with reference to the description below.
4.
Click the
When assigning LX/LY1000 to 15FF (1536 points) equally to the I/O range between the I/O master station
Ex.
and station No.2 to No.4
X/Y Equal
Assignment
5.
Equal assignment is done in "LX/LY Setting(1)" of "Assignment the CC IE Control Network
Range".
194
Page 183, Section 6.3)
button.
button.
Item
Set the start station.
Start Station
(Setting range for Universal model QCPU: 1 to 120, Default: None)
(Setting range for other than Universal model QCPU: 1 to 64, Default: None)
Set the end station.
End Station
(Setting range for Universal model QCPU: 1 to 120, Default: None)
(Setting range for other than Universal model QCPU: 1 to 64, Default: None)
Set the start number of the LX/LY for equal assignment.
Start No.
(Setting range: 0000
Total Points
Set the total points of LX/LY, which are to be assigned equally.
Assigned
(Setting range: 16 to 8192, Default: None)
Description
to 1FF0
, Default: None)
H
H