Mitsubishi Electric MELSEC Q Series Reference Manual page 578

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

No.
Name
Own station's IN-side
SB006E
error frame detection
Own station's OUT-side
SB006F
error frame detection
Station No. setting
SB0070
status (own station)
IP address setting
SB007F
status
Path switching
SB008E
detection flag
SB008F
Transient error
Hardware test
SB0090
completion status
Hardware test
SB0091
normal/error
completion status
Self-loopback test
SB0092
completion status
Self-loopback test
SB0093
normal/error
completion status
576
Stores whether the error frame is received or not in the IN-side of the own
station from power-on to the present.
OFF: Error frame not received
ON: Error frame received
Stores whether the error frame is received or not in the OUT-side of the own
station from power-on to the present.
OFF: Error frame not received
ON: Error frame received
Stores the station No. setting status of the own station when using the UINI
instruction for station No. setting.
OFF: Station No. determined
ON: Station No. not yet determined
A determined station No. of the own station can be confirmed in Station No.
(SW0042).
Stores the IP address setting using the parameter.
OFF: No setting
ON: Set
When the station is a normal station, the reception status of an IP address
from the control station is stored.
Stores the path switching detection status.
OFF: Path switching not detected
ON: Path switching detected
The stored value is cleared when Clear loop switching counter (SB0009) is
turned ON.
Stores the transient transmission error detection status.
OFF: Error not detected
ON: Error detected
When an error is detected, the number of errors can be checked in Transient
transmission error (SW006F).
Stores the completion status of hardware test.
OFF: Not executed or being executed
ON: Completed
When completed, the completion status can be checked in Hardware test
normal/error completion status (SB0091).
Stores the normal or error completion status of the hardware test.
OFF: Completed normally
ON: Failed
(Condition)
• Valid when Hardware test completion status (SB0090) is ON.
Stores the completion status of the self-loopback test.
OFF: Not executed or being executed
ON: Completed
When completed, the completion status can be checked in Self-loopback test
normal/error completion status (SB0093).
Stores the normal or error completion status of self-loopback test.
OFF: Completed normally
ON: Failed
(Condition)
• Valid when Self-loopback test completion status (SB0092) is ON.
Description
Availability
Control
Normal
station
station
×