Mitsubishi Electric MELSEC Q Series Reference Manual page 281

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(2) Devices used in the program example
(a) Special relay (SM), link special relay (SB), and link special register (SW)
Device
SM402
Turned ON for only one scan after RUN
SB0047
Baton pass status of own station
(b) Devices used by the user
Device
M1000
Completion device (READ instruction)
Completion status indication device (READ
M1001
instruction)
M1010
Execution command (READ instruction)
M1020
Completion device (WRITE instruction)
(3) Link dedicated instruction settings
The following shows settings of control data for the READ and WRITE instructions.
(a) READ instruction
Device
(S1)+0
D1000
Error completion type
(S1)+1
D1001
Completion status
(S1)+2
D1002
Channel used by own station
(S1)+3
D1003
Target station's CPU type
(S1)+4
D1004
Target station network No.
(S1)+5
D1005
Target station No.
(S1)+6
D1006
(Unused)
(S1)+7
D1007
Number of resends
(S1)+8
D1008
Arrival monitoring time
(S1)+9
D1009
Read data length
(S1)+10 D1010
(Unused)
Description
Description
Item
0001
(Clock data at the time of error completion is not set)
H
— (Set by system, no setting required)
1
0000
(Control CPU)
H
1
2
0
5 times
0 (10 seconds)
50 words
0
CHAPTER 8 PROGRAMMING
Device
Description
SW00A0.1
Baton pass status of station No.2
Device
Description
Completion status indication device (WRITE
M1021
instruction)
M1030
Execution command (WRITE instruction)
D1000 to
Control data (READ instruction)
D1010
D1020 to
Control data (WRITE instruction)
D1030
Setting value
8
279