Mitsubishi Electric MELSEC Q Series Reference Manual page 188

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(1) Assuring 32-bit data integrity
When settings are configured with the following four conditions met, 32-bit data integrity is automatically assured.
(
Page 76, Section 4.1.5)
• The start device No. of LB is a multiple of 20
• The points assigned per station in LB is a multiple of 20
• The start device No. of LW is a multiple of 2.
• The points assigned per station in LW is a multiple of 2.
(2) Using equal assignment
The link device range can be equally assigned to each send range of the relevant stations.
1.
Open the "Network Range Assignment" window in the programming tool. (
6.3)
2.
Click the
3.
Configure settings with reference to the description below.
4.
Click the
When assigning LB0 to 7FF (2048 points) equally to the send ranges of station Nos. 1 to 4
Ex.
Item
Assignment target
B/W Equal
Assignment
186
button.
button.
Select "LB/LW Setting(1)" or "LB/LW Setting(2)".
Set the start station.
Start Station
(Setting range for Universal model QCPU: 1 to 120, Default: None)
(Setting range for other than Universal model QCPU: 1 to 64, Default: None)
Set the end station.
End Station
(Setting range for Universal model QCPU: 1 to 120, Default: None)
(Setting range for other than Universal model QCPU: 1 to 64, Default: None)
Set the start number of the LB/LW for equal assignment.
• LB (Setting range: 0000
Start No.
• LW (Setting range: 0000
Set the total points of LB/LW, which are to be assigned equally.
Total Points
• LB (Setting range: 16 to 32768, Default: None)
Assigned
• LW (Setting range: 1 to 131072, Default: None)
.
H
.
H
Description
to 7FF0
, Default: None)
H
H
to 1FFFF
, Default: None)
H
H
Page 183, Section

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71gp21-sxMelsec qj71gp21s-sx