Mitsubishi Electric MELSEC Q Series Reference Manual page 357

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Device
Item
(S1)+1
Completion status
Channel used by
(S1)+2
*2
own station
Target station's
(S1)+3
CPU type
Target station
(S1)+4
network No.
Setting data
The instruction completion status is stored.
0: Normal
Other than 0: Error (
Page 511, Section 10.2)
Specify the channel used by the own station. (
Section 9.2.2 (1))
Specify the CPU module on the station to be accessed.
Setting value
Control CPU (The access target is the same as
0000
H
when "03FF
H
03D0
Control system CPU (Redundant CPU only)
H
03D1
Standby system CPU (Redundant CPU only)
H
03D2
System A CPU (Redundant CPU only)
H
03D3
System B CPU (Redundant CPU only)
H
• Target station CPU (single CPU system)
• Multi-CPU No.1
03E0
H
• Control CPU (single CPU system)
• Multiple CPU system No.1
03E1
Multiple CPU system No.2
H
03E2
Multiple CPU system No.3
H
03E3
Multiple CPU system No.4
H
03FF
Control CPU
H
When the instruction is executed with control system CPU (03D0
or standby system CPU (03D1
) specified, if system switching
H
occurs at the target station, the instruction execution may fail. (Error
code: 4244
, 4248
)
H
H
If the instruction has failed with the above error, execute it again.
Specify the network No. of the target station.
1 to 239: Network No.
254: Specify this when 254 has been set in Jn.
CHAPTER 9 DEDICATED INSTRUCTIONS
Page 328,
Description
" is specified.)
Setting
Setting range
side
System
1 to 10
(1 to 8 when the
User
own station is a
safety CPU)
0000
H
03D0
to 03D3
H
H
User
03E0
to 03E3
H
H
03FF
H
)
H
1 to 239
User
254
9
*1
355