Mitsubishi Electric MELSEC Q Series Reference Manual page 309

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(b) Cyclic transmission restart of another station
1.
In the following link special register (SW), specify a station for restarting cyclic transmission.
• Specification of target station
Link stop/startup direction (SW0000)
• Specification of station No.
Link stop/startup direction (SW0001 to SW0008)
• Specification of group
Group specification for link stop/startup (SW0012 to SW0013)
2.
Turn System link startup (SB0002) ON.
3.
When the CC-Link IE Controller Network module accepts a request, Cyclic transmission start
accept status (SB0050) is turned ON.
4.
When the cyclic transmission restart is completed, Cyclic transmission start
completion status (SB0051) is turned ON.
5.
If the cyclic transmission restart is completed abnormally, an error code will be stored in Data
linking start status (entire system) (SW0051).
6.
Turn System link startup (SB0002) OFF.
No.
SB0002
System link startup
SB0003
System link stop
Cyclic transmission start accept status
SB0050
(system)
Cyclic transmission start completion status
SB0051
(system)
Cyclic transmission stop accept status
SB0052
(system)
Cyclic transmission stop completion status
SB0053
(system)
(c) Cyclic transmission stop of own station
1.
Turn Link stop (own station) (SB0001) ON.
2.
When the CC-Link IE Controller Network module accepts a request, Cyclic transmission stop
accept status (own station) (SB004E) is turned ON.
3.
When the cyclic transmission stop is completed, Cyclic transmission stop completion status (own
station) (SB004F) is turned ON.
4.
If the cyclic transmission stop is completed abnormally, an error code will be stored in Data
linking stop status (own station) (SW004F).
5.
Turn Link stop (own station) (SB0001) OFF.
Description
CHAPTER 8 PROGRAMMING
No.
Description
SW0000
Link stop/startup direction
SW0001 to
SW0008
SW0012 to
Group specification for link stop/startup
SW0013
SW004A
Data linking stop request station
SW0051
Data linking start status (entire system)
SW0053
Data linking stop status (entire system)
8
307

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71gp21-sxMelsec qj71gp21s-sx

Table of Contents