(e) Comparison of other functions
Interrupt request to CPU module
Multiplex transmission function
Increase of send points by mounting multiple network modules of the
same network No.
Debug mode
Simplified duplexing of network
Redundant system
618
Function
: compatible,
Compatibility
Precautions for replacement
The CC-Link IE Controller Network module
does not have an interrupt of scan completion.
Replace with other interrupt condition.
The CC-Link IE Controller Network module
does not have this function.
The high-speed communication can be
realized without multiplex transmission
function in the CC-Link IE Controller Network
module since link scan time of the CC-Link IE
Controller Network is shorter than that of the
MELSECNET/H module.
Check the software version.
(
Page 606, Appendix 3)
The CC-Link IE Controller Network module
does not have this function.
• For the CC-Link IE Controller Network
module, the system switching monitoring
time is set with a network parameter.
Since it has been set with SB0018/SW0018
for the MELSECNET/H, delete the relevant
part of the existing sequence program.
• When the CC-Link IE Controller Network
module is used, link output (LY) data cannot
be sent from the standby system station.
• The circuit test or station-to-station test must
be executed in separate mode for the CC-
Link IE Controller Network module.
: partially changed, —: incompatible