(b) Checking for cable faults of own station
1.
When an own station cable has fault, any of SB0066 to SB0069 and SB006C to SB006F is turned
ON.
2.
The rate of line error occurrence can be checked in SW0068 to SW0069 and SW006A to SW006B.
When Clear IN-side transmission error counter (SB0007) is turned ON, SB006E and SW0068 to SW0069
can be cleared.
When Clear OUT-side transmission error counter (SB0008) is turned ON, SB006F and SW006A to
SW006B can be cleared.
No.
SB0007
Clear IN-side transmission error counter
SB0008
Clear OUT-side transmission error counter
SB0066
Own station's IN-side link-up status
SB0067
Own station's OUT-side link-up status
SB0068
Own station's IN-side link establishing status
SB0069
Host station OUT-side link establishment status SW0069
Own station's IN-side error frame reception
SB006C
status
Own station's OUT-side error frame reception
SB006D
status
SB006E
Own station's IN-side error frame detection
SB006F
Own station's OUT-side error frame detection
312
Description
No.
SW0068
IN-side line error occurrence rate (Max.)
IN-side line error occurrence rate (present.)
SW006A
OUT-side line error occurrence rate (Max.)
SW006B
OUT-side line error occurrence rate (present.)
Description