Mitsubishi Electric MELSEC Q Series Reference Manual page 576

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

No.
Name
Cyclic transmission
SB0053
stop completion status
(system)
Parameter receive
SB0054
status
Received parameter
SB0055
error
SB0056
Communication status
SB005A
Parameter type
Own station's CPU
SB005B
RUN status
I/O master station
SB005C
(Block 1)
I/O master station
SB005D
(Block 2)
Own station's CPU
SB005E
type
574
Turned ON when Cyclic transmission stop accept status (system)(SB0052) is
turned ON and cyclic transmission stop is completed.
OFF: Stop uncompleted (SB0003 is OFF)
ON: Stop completed (SB0003 is ON)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
Stores the status of receiving parameters.
The parameter receive status from the CPU module is stored for the control
station.
The parameter receive status from the control station is stored for the normal
station.
OFF: Receive completed
ON: Receive uncompleted
Stores the status of received parameter (Own parameter status is stored for
the control station)
OFF: Parameter normal
ON: Parameter error
Stores the transient transmission status.
OFF: Transient transmission by control station
ON: Transient transmission by sub-control station
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
Stores Network Type of the control station.
OFF: CC IE Control
ON: CC IE Control Extended Mode
Stores the RUN status of the CPU module of the own station.
OFF: RUN, STEP-RUN
ON: The CPU module stop due to STOP, PAUSE, or error
Stores the I/O master station setting status of block 1.
OFF: No setting
ON: Setting set
When the setting is set, the station No. is stored into I/O master station (Block
1) (SW005C).
(Condition)
• Valid when Data link status of own station (SB0049) is OFF.
Stores the I/O master station setting status of block 2.
OFF: No setting
ON: Setting set
When the setting is set, the station No. is stored into I/O master station (Block
2) (SW005D).
(Condition)
• Valid when Data link status of own station (SB0049) is OFF.
Stores the CPU type of the own station.
OFF: Other than Basic model QCPU and safety CPU
ON: Basic model QCPU or safety CPU
Description
Availability
Control
Normal
station
station