Mitsubishi Electric MELSEC Q Series Reference Manual page 319

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(b) Checking parameter status of own station
1.
When receiving parameters is completed, Parameter receive status (SB0054) is turned OFF.
2.
When parameters have an error, Received parameter error (SB0055) is turned ON and an error
code is stored in Parameter setting status (SW0055).
3.
The presence or absence of parameters can be checked with Parameter information (SW0054).
No.
SB0054
Parameter receive status
SB0055
Received parameter error
4.
When the parameters are reflected in the CC-Link IE Controller Network module, contents of
parameters are stored in the following link special relay (SB) and link special register (SW).
No.
SB0040
Network type (own station)
SB0043
Online switch (own station)
SB0044
Station setting (own station)
SB0048
Control station status (own station)
SB0056
Communication status
SB005C
I/O master station (Block 1)
SB005D
I/O master station (Block 2)
SB005E
Own station's CPU type
SB0060
Communication mode
SB0061
Cyclic transmission punctuality assurance
SB007F
IP address setting status
SB00C0
Reserved station specification
Description
Description
CHAPTER 8 PROGRAMMING
No.
Description
SW0054
Parameter information
SW0055
Parameter setting status
No.
Description
SW0040
Network No.
SW0041
Group No.
SW0042
Station No.
SW0043
Mode status
SW0044
Station setting
SW0046
Module type
SW004C
Shared group No.
SW0056
Current control station
SW0057
Designated control station
SW0059
Total number of link stations
SW005C
I/O master station (Block 1)
SW005D
I/O master station (Block 2)
SW0063
Communication mode
SW00C0
to
Reserved station specification
SW00C7
8
317