No.
Name
SW00B0
Cyclic transmission
to
status of each station
SW00B7
SW00C0
Reserved station
to
specification
SW00C7
Stores the cyclic transmission status of each station.
0: Cyclic transmission normally operating station
1: Cyclic transmission faulty station
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW00B0 16 15 14 13 12 11 10
SW00B1
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW00B2
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW00B3
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW00B4
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW00B5
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW00B6
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW00B7
-
-
-
-
-
Each number in the table represents station No.
If a CPU module installed together with the CC-Link IE Controller Network
module with external power supply function is turned OFF, detection of a data
link error may take more time than usual.
For immediate detection of a data link error, program an interlock using the
link relay (LB) in each station's send range.
(
Page 275, Section 8.1.3)
When group cyclic transmission is used, a station whose shared group is
different from the group of the own station is detected as a cyclic transmission
error station. (Including reserved stations)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• The station No. later than the largest one are excepted.
Stores the setting status of reserved station.
0: Other than reserved station
1: Reserved station
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW00C0 16 15 14 13 12 11 10
SW00C1
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW00C2
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW00C3
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW00C4
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW00C5
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW00C6
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW00C7
-
-
-
-
-
Each number in the table represents station No.
(Condition)
• Valid when Data link status of own station (SB0049) is OFF.
• The station No. later than the largest one are excepted.
Description
9
8
7
6
5
4
3
-
-
- 120 119 118 117 116 115 114 113
9
8
7
6
5
4
3
-
-
- 120 119 118 117 116 115 114 113
APPENDICES
Availability
Control
Normal
station
station
2
1
2
1
595
A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71gp21-sxMelsec qj71gp21s-sx

Table of Contents