10.1.10
Data link is disabled on a station of a Basic model QCPU or
safety CPU
The following flowchart shows the procedures to be taken when data link is disabled on a station of a Basic model
QCPU or safety CPU.
Data link is disabled on a Basic model
QCPU or safety CPU station.
Is the CC-Link IE Controller
Network module's function
version D or later?
Is the Basic model QCPU's
function version B or later?
Has a LINK PARA. ERROR
occurred in a Basic model
QCPU, or a NETWORK
PARAMETER ERROR
in a safety CPU?
Cyclic transmission is disabled
Page 502, Section 10.1.6
510
Yes
Yes
No
End
No
Use a CC-Link IE Controller Network module of
function version D or later.
No
Use a Basic model QCPU of function version B
or later.
Check the network parameters.
Check the own station send range in LB/LW of
Yes
the Basic model QCPU and the safety CPU
station in the network range assignment setting
for the control station.