No.
Name
Link startup
SB0000
(own station)
SB0001
Link stop (own station)
SB0002
System link startup
SB0003
System link stop
Clear communication
SB0006
error count
Clear IN-side
SB0007
transmission error
counter
Description
Restarts cyclic transmission of own station.
OFF: Startup not directed
ON: Startup directed (valid at rising)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only when one of SB0000 to SB0003 is turned ON.
Stops cyclic transmission of own station.
OFF: Stop not directed
ON: Stop directed (valid at rising)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only when one of SB0000 to SB0003 is turned ON.
Restarts cyclic transmission of the entire system.
The station to restart cyclic transmission can be specified by Link stop/startup
direction (SW0000 to SW0008) or Group specification for link stop/startup
(SW0012 to SW0013).
OFF: Startup not directed
ON: Startup directed (valid at rising)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only when one of SB0000 to SB0003 is turned ON.
Stops cyclic transmission of the entire system.
The station to stop cyclic transmission can be specified by Link stop/startup
direction (SW0000 to SW0008) or Group specification for link stop/startup
(SW0012 to SW0013).
OFF: Stop not directed
ON: Stop directed (valid at rising)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only when one of SB0000 to SB0003 is turned ON.
Clears the communication error count that is displayed at CC IE Control
diagnostics into 0.
OFF: Clear not directed
ON: Clear directed (Number of errors is not counted during ON)
Clears the IN-side line error detection area (SW0068, SW0069, SB006E,
SB0140, SW0074, SW0140 to SW0147) into 0.
OFF: Clear not directed
ON: Clear directed (Number of errors is not counted during ON)
APPENDICES
Availability
Control
Normal
station
station