Mitsubishi Electric MELSEC Q Series Reference Manual page 571

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

No.
Name
Link startup
SB0000
(own station)
SB0001
Link stop (own station)
SB0002
System link startup
SB0003
System link stop
Clear communication
SB0006
error count
Clear IN-side
SB0007
transmission error
counter
Description
Restarts cyclic transmission of own station.
OFF: Startup not directed
ON: Startup directed (valid at rising)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only when one of SB0000 to SB0003 is turned ON.
Stops cyclic transmission of own station.
OFF: Stop not directed
ON: Stop directed (valid at rising)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only when one of SB0000 to SB0003 is turned ON.
Restarts cyclic transmission of the entire system.
The station to restart cyclic transmission can be specified by Link stop/startup
direction (SW0000 to SW0008) or Group specification for link stop/startup
(SW0012 to SW0013).
OFF: Startup not directed
ON: Startup directed (valid at rising)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only when one of SB0000 to SB0003 is turned ON.
Stops cyclic transmission of the entire system.
The station to stop cyclic transmission can be specified by Link stop/startup
direction (SW0000 to SW0008) or Group specification for link stop/startup
(SW0012 to SW0013).
OFF: Stop not directed
ON: Stop directed (valid at rising)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only when one of SB0000 to SB0003 is turned ON.
Clears the communication error count that is displayed at CC IE Control
diagnostics into 0.
OFF: Clear not directed
ON: Clear directed (Number of errors is not counted during ON)
Clears the IN-side line error detection area (SW0068, SW0069, SB006E,
SB0140, SW0074, SW0140 to SW0147) into 0.
OFF: Clear not directed
ON: Clear directed (Number of errors is not counted during ON)
APPENDICES
Availability
Control
Normal
station
station
A
569