No.
Name
SW0041
Group No.
SW0042
Station No.
SW0043
Mode status
SW0044
Station setting
SW0046
Module type
Baton pass status
SW0047
(own station)
Stores the group No. of own station.
0: No group specification
1 to 32: Group No.
Stores the station No. of own station.
1 to 120: Own station No. (Station No. setting status (own station)
(SB0070) is OFF.)
255: Station No. not yet determined (Station No. setting status
(own station) (SB0070) is ON.)
Stores the operation mode of the own station.
0: Online
2: Offline
5: Station-to-station test
6: Circuit test
7: Self-loopback test
9: Hardware test
Stores the setting status of own station.
b15b14
to
b6
0
to
SW0044
CPU type
0: Other than Basic model QCPUs and
safety CPUs
1: Basic model QCPU or safety CPU
Stores the hardware status of own station.
b15
b14
to
b9
b8
b7 b6 b5 b4 b3
SW0046
0
to
0
*
b15: Variable (used in the system)
Stores the communication status of own station.
0: Data linking
1: Data link stop in execution
2: Baton pass being executed
3: Baton pass stop in execution
4: Test being executed
5: Offline
Description
b5
b4
b3
b2 b1 b0
0
0
0
Network type
(01: Controller network)
Station type
(0: Normal station, 1: Control station)
Normal station parameter
0: No normal station parameter
1: Normal station parameter
Mode
0: CC IE Control
1: CC IE Control Extended Mode
b2
b1
b0
Transmission path information 1
(00: Optical)
Transmission path information 2
(0: Duplex system)
Topology
(0: Loop type)
Cable type
(0: Supports SX)
External power supply function
(0: Not provided, 1: Provided)
Model type
001: Module
010: Board
110: HMI
APPENDICES
Availability
Control
Normal
station
station
A
587