Mitsubishi Electric MELSEC Q Series Reference Manual page 242

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(2) Precautions
(a) Transient transmission range
Communication can be made with a station on the eighth farthest network system. (No. of relay stations: 7)
(b) Access conditions when the station No. of the request source, request target or CC-
Link IE Controller Network relay station is 65 or more.
When the station number of the request source or request destination is 65 or more, access can be made
under the following conditions.
• The request source and target are Universal model QCPUs.
• The CC-Link IE Controller Network relay station is a Universal model QCPU.
Programming tool
When the CC-Link IE Controller Network relay station No. is 65 or more, access is available under the following
conditions.
• The request source is a Universal model QCPU.
• The CC-Link IE Controller Network relay station is a Universal model QCPU.
(Request source)
Programming tool
240
(Relay station)
1M
1
1N
P
CC-Link IE Controller Network
1N
120
1N
S
(Request source)
1M
1
1N
64
P
S
CC-Link IE Controller Network
1N
65
1N
120
S
S
(Relay station)
(Request target)
64
2M
1
2N
S
P
MELSECNET/H, etc.
65
S
MELSECNET/H, etc.
2M
1
2N
P
S
(Request target)
64
S
Universal model QCPU
64
Universal model QCPU

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71gp21-sxMelsec qj71gp21s-sx

Table of Contents