(c) Transmission delay time for the SREAD/SWRITE instruction
Sending station
TD1 = {(ST + T) × 2 + LS × 11 + (SR + R)} × (m + 1)
Non-redundant system
Redundant system
TD1 + TsT × 2 × (m + 1)
Sending station
TD2 = {(ST + T) × 2 + LS × 11 + (SR + R + TsR)} × (m + 1) TD3 = {(ST + T) × 2 + LS × 11 + TsR} × (m + 1)
Non-redundant system
Redundant system
TD2 + TsT × 2 × (m + 1)
Sending station
Access to control system CPU through standby
TD4 = {(ST + T) × 2 + LS × 11 + (SR + R + TsR) + 6} ×
Non-redundant system
(m + 1)
Redundant system
TD4 + TsT × 2 × (m + 1)
TD1 to TD5: Transmission delay time for the SREAD/SWRITE instruction
ST:
Sequence scan time on sending side (except link refresh time and scan time delay due to tracking
transfer)
SR: Sequence scan time on receiving side (except link refresh time and scan time delay due to tracking
transfer)
T:
Link refresh time on sending side (Total of the number of mounted network modules)
R:
Link refresh time on receiving side (Total of the number of mounted network modules)
m:
Number of fragmented transmissions = (Read or write data length) / 960 (Rounded up to the nearest
integer)
TsT: Scan time delay due to tracking transfer on the sending side
TsR: Scan time delay due to tracking transfer on the receiving side
LS:
Link scan time
*1
For the scan time delay due to tracking transfer, refer to the following.
QnPRHCPU User's Manual (Redundant System)
258
Transmission delay time of when the receiving station is a non-redundant system [ms]
Transmission delay time of when the receiving station is a redundant system and
transmission does not pass through a tracking cable [ms]
Redundant system (control system CPU)
Transmission delay time of when the receiving station is a redundant system and
transmission passes through a tracking cable [ms]
system
Redundant system (standby system CPU)
TD3 + TsT × 2 × (m + 1)
Access to standby system CPU through
control system
TD5 = {(ST + T) × 2 + LS × 11 + TsR + 6} ×
(m + 1)
TD5 + TsT × 2 × (m + 1)
*1
*1