Mitsubishi Electric MELSEC Q Series Reference Manual page 591

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

No.
Name
Own station's CPU
SW004B
status
SW004C
Shared group No.
Data linking start
SW004D
status (own station)
Data linking stop
SW004F
status (own station)
Data linking start
SW0051
status (entire system)
Data linking stop
SW0053
status (entire system)
Stores the CPU module status of the own station.
01
: STOP (Normal)
H
02
: STOP (Stop error is occurring)
H
03
: STOP (Continuation error is occurring)
H
04
: RUN (Normal)
H
05
: RUN (Continuation error is occurring)
H
06
: STEP-RUN
H
07
: PAUSE
H
0E
: CPU module being reset
H
0F
: CPU module initial processing in execution
H
Stores shared group No. of the own station.
0: No shared group setting
1 to 120: Shared group No.
Stores the result of starting cyclic transmission with Link startup (own station)
(SB0000).
0: Normal
1 or later: Error (
Page 511, Section 10.2)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
Stores the result of stopping cyclic transmission with Link stop (own station)
(SB0001).
0: Normal
1 or later: Error (
Page 511, Section 10.2)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
Stores the result of starting cyclic transmission with System link startup
(SB0002).
0: Normal
1 or later: Error description of own station
(
Page 511, Section 10.2)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
Stores the result of stopping cyclic transmission with System link stop
(SB0003).
0: Normal
1 or later: Error description of own station
(
Page 511, Section 10.2)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
Description
APPENDICES
Availability
Control
Normal
station
station
A
589