(2) When a programming tool connected station is faulty
Control station
No.1
Normal
Selected
station
station
No.8
550
Normal station
No.2
Normal station
No.3
Select the own station.
Stations equivalent to the maximum number of stations that can be
connected are displayed due to a parameter error.
An error has occurred in the station No.8.
Click the error details button.
The Error Factor field indicates that the station No.8 is larger than
the total station No. per network.
Take corrective actions according to the troubleshooting.