Mitsubishi Electric MELSEC Q Series Reference Manual page 594

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

No.
Name
IN-side line error
SW0068
occurrence rate (Max.)
IN-side line error
SW0069
occurrence rate
(present.)
OUT-side line error
SW006A
occurrence rate (Max.)
OUT-side line error
SW006B
occurrence rate
(present.)
Number of loop
SW006E
switches
Transient transmission
SW006F
error
IN-side loopback
SW0070
station No.
IN-side loopback
SW0071
factor
592
Stores the rate (maximum value) of receiving error frame at the IN-side of own
station. (Unit: %)
The accumulation of errors is cleared when Clear IN-side transmission error
counter (SB0007) is turned ON.
Stores the rate (present value) of receiving error frame at the IN-side of own
station. (Unit: %)
The accumulation of errors is cleared when Clear IN-side transmission error
counter (SB0007) is turned ON.
Stores the rate (maximum value) of receiving error frame at the OUT-side of
own station. (Unit: %)
The accumulation of errors is cleared when Clear OUT-side transmission error
counter (SB0008) is turned ON.
Stores the rate (present value) of receiving error frame at the OUT-side of own
station. (Unit: %)
The accumulation of errors is cleared when Clear OUT-side transmission error
counter (SB0008) is turned ON.
Stores the number (accumulation) of switching communication paths.
When Clear loop switching counter (SB0009) turns ON, the number is
cleared.
Stores the number (accumulation) of transient transmission errors.
The number of errors is cleared when Clear transient transmission error
counter (SB000A) is turned ON.
Stores the station No. of the station where a loopback is executed at IN-side.
0: No station executes loopback
1 to 120: Station No.
255: Station No. not set
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
Stores the factor of IN-side loopback.
00
: No station executes loopback
H
02
: OUT-side cable disconnection
H
03
: OUT-side cable insertion error
H
04
: OUT-side line establishing
H
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
Description
Availability
Control
Normal
station
station