Mitsubishi Electric MELSEC Q Series Reference Manual page 517

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Error code
Error
IP packet transfer function not
E01D
supported (IP communication
H
test)
E101
Parameter error
H
E102
Reserved own station error
H
E103
Invalid own station No.
H
E104
H
to
Parameter error
E10A
H
E10B
H
Parameter error
E10C
H
E10D
Network module error
H
E110
H
to
Parameter error
E117
H
E11A
Start device No. error (LW)
H
E11B
Start device No. error (LB)
H
E11C
LB/LW setting (2) error (LW)
H
E11D
LB/LW setting (2) error (LB)
H
E11E
End device No. error (LW)
H
E11F
End device No. error (LB)
H
UINI execution at control
E120
H
station
Own station No. error (UINI
E121
H
instruction)
Error detail
The CPU module which has
detected an error does not
support the IP packet transfer
function.
Some of the network
parameters is incorrect.
The own station was set as a
reserved station.
The own station No. set is
outside the range of total
stations.
Some of the network
parameters is incorrect.
The CPU module or CC-Link
IE Controller Network module
does not support the added
function.
The hardware has failed.
Some of the network
parameters is incorrect.
The Basic model QCPU or
safety CPU's own send range
is set to LB/LW4000 or
higher.
The Basic model QCPU or
safety CPU's own send range
is set in "LB/LW Setting(2)".
The Basic model QCPU or
safety CPU's own send range
is set to LB/LW4000 or
higher.
The UINI instruction was
executed at a control station.
With "Specify Station No. by
Parameter" selected in the
network parameters, the UINI
instruction was executed.
CHAPTER 10 TROUBLESHOOTING
Corrective action
• Check the serial number (first five digits) of the CPU
module to check whether the module supports the
function.
If the module does not support the function, replace it
with the CPU module of the latest version.
• Write correct network parameters to the programmable
controller.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
• Cancel the reserved station setting in "Network Range
Assignment" of the control station.
• Change the station No. to the one that is not specified
as a reserved station.
• Increase the number of total stations in the network
setting of the control station.
• Change the station number to the one that is within the
number of total stations.
• Write correct network parameters to the programmable
controller.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
• Use a CPU module or CC-Link IE Controller Network
module that supports the added function.
Page 606, Appendix 3
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
• Please consult your local Mitsubishi representative.
• Write correct network parameters to the programmable
controller.
• If the error persists even after taking the above action,
please consult your local Mitsubishi representative.
• Check "LB/LW Setting(1)" in "Network Range
Assignment" of the control station.
• Check "LB/LW Setting(2)" in "Network Range
Assignment" of the control station.
• Check "LB/LW Setting(1)" in "Network Range
Assignment" of the control station.
• Setting the station number with the UINI instruction is
not allowed for control stations.
Set it with a network parameter.
• Change the station type setting to Normal station, and
then retry it.
• Select "Specify Station No. by Program." in the network
parameters, and execute it again.
10