Mitsubishi Electric MELSEC Q Series Reference Manual page 599

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

No.
Name
SW00F0
CPU RUN status of
to
each station
SW00F7
SW0100
CPU operation status
to
of each station (1)
SW0107
Stores the RUN status of the CPU module of each station. (Including own
station)
0: RUN, STEP-RUN
1: STOP, PAUSE, stop error
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW00F0 16 15 14 13 12 11 10
SW00F1
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW00F2
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW00F3
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW00F4
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW00F5
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW00F6
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW00F7
-
-
-
-
-
Each number in the table represents station No.
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only for the normally operating station at Baton pass status of each
station (SW00A0 to SW00A7)
• The reserved station and the station No. later than the largest one are
excepted.
Stores the stop error status of the CPU module of each station. (Including own
station)
0: Normal
1: Stop error
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW0100 16 15 14 13 12 11 10
SW0101
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW0102
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW0103
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW0104
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW0105
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW0106
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW0107
-
-
-
-
-
Each number in the table represents station No.
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only for the normally operating station at Baton pass status of each
station (SW00A0 to SW00A7)
• The reserved station and the station No. later than the largest one are
excepted.
Description
9
8
7
6
5
4
3
-
-
- 120 119 118 117 116 115 114 113
9
8
7
6
5
4
3
-
-
- 120 119 118 117 116 115 114 113
APPENDICES
Availability
Control
Normal
station
station
2
1
2
1
597