M800/M80/E80/C80 Series Alarm/Parameter Manual
5 System Alarms (Z)
Z34
DeviceNet error
Details
Any of the following errors has occurred in the DeviceNet unit.
Master function error (X03 is ON)
Slave function error (X08 is ON)
Message communication error (X05 is ON)
If the errors have occurred in more than one unit, the error No. of the unit with the smallest slot No. is displayed.
If the master function, slave function and message communication errors have occurred at the same time, the
error is displayed in the following priority order.
1. Master function error
2. Slave function error
3. Message communication error
Remedy
Select the [Ext. PLC link control] menu on the maintenance screen to open the unit confirmation screen,
and check the unit in error and details to cancel the error.
Z35
Direct Socket connection error
Details
- Connection has failed.
- Five or more clients attempted a connection.
Remedy
Check the connection of the network cables, and check for broken wires and a failure of the network con-
nection devices such as hub.
When using the Direct Socket communication I/F, connect up to four clients.
Z35
Direct Socket receive error
Details
- Receiving data from a client has failed.
Remedy
Check the connection of the network cables, and check for broken wires and a failure of the network con-
nection devices such as hub.
Z35
Direct Socket send error
Details
- Sending data to a client has failed.
Remedy
Check the connection of the network cables, and check for broken wires and a failure of the network con-
nection devices such as hub.
Z35
Direct Socket timeout error
Details
There was no response from client computers, and a timeout error occurred.
Remedy
Check the connection of the network cables, and check for broken wires and a failure of the network con-
nection devices such as hub.
Z35
Direct Socket comm OFF
Details
The direct Socket communication I/F is OFF.
Remedy
Check the parameter "#11051 Direct Socket ON".