M800/M80/E80/C80 Series Alarm/Parameter Manual
16 Machine Parameters
#1218
aux02
bit3: Parameter input/output format
Select the parameter input/output format.
0: Type I
Displayed on one line per parameter.
(Example)
N1001T1P1
N1001T2P1
N1001T3P0
1: Type II
Data with the same parameter number is displayed on the same line.
(Example)
N1001 T1 P1 T2 P1 T3 P0
bit4: External workpiece coordinate offset tool number selection
Select the R register that contains the tool number used for automatic calculation when measuring the coor-
dinate offset of an external workpiece.
0: Follow the setting of "#1130 set_t".
1: Use the tool number indicated by user PLC.
bit5: Parameter I/O II spindle specification address
Select the spindle specification address of parameter I/O type II.
0: C
1: T
This parameter is also applied to the spindle specification address for input and verification.
(Note) This parameter is valid only for parameter I/O type II (when "#1218 aux02/bit3" is set to "1").
bit6: Set No. valid when program input
Select which program No. is applied when inputting programs in "#1 MAIN PROGRAM" on Data I/O screen.
0: The No. in the input data
1: The No. set in the data setting area
bit7: Input by program overwrite
(1) Select the operation when the program to be input in "#1 MAIN PROGRAM" on Data I/O screen, has al-
ready been registered.
0: An operation error (E65) occurs.
1: Input by overwrite.
(2) Select the operation in the high-speed program server mode, when the name of the file to be transmitted
with (IC -> host) transmission already exists in the host.
0: Prohibit overwrite
1: Enable overwrite