M800/M80/E80/C80 Series Alarm/Parameter Manual
16 Machine Parameters
16.33 CC Link IE Field Parameters [M8]
16.33.1 CC Link IE Field Network 1
(PR)
#82000
Select the slot of the CC-Link IE field network expansion unit to which you apply the CCIEF common param-
eters #82000 to #82695.
* If you select the same slot as of "#82700 #2 Slot No.", the parameters #82000 to #82695 are applied to the
slot with higher priority.
---Setting range---
0: No setting (Disable)
1: EXT3
2: EXT4
* For M80/M800S/E80
1: EXT1
2: EXT2
(PR)
#82001
Specify the station type of the CC-Link IE field network expansion unit.
0: Master station
1: Local station
(PR)
#82002
Specify the network No. of the CC-Link IE field network expansion unit.
---Setting range---
0 to 239
0: No setting
#82003
Specify the number of stations other than master stations.
If the NC acts as a local station, set 0 in the parameter.
If you set a reserved station, include it in the count.
---Setting range---
0 to 64
0: No setting
(PR)
#82004
Specify the station No. of the CC-Link IE field network expansion unit.
For a master station, the station No. is 0, irrespective of the parameter.
* If the NC acts as a master station, the maximum value of the station No. which can be set to the slave station
is "64". If the NC acts as a master station and also the NC is connected as a local station, set "64" or less
to the station No.
---Setting range---
0 to 120
(PR)
#82005
Specify the communication mode.
0: Online mode
1: Offline mode
2: H/W test mode
#82006
Select whether to hold or clear the input data from the slave station where a data link error occurred.
0: Clear
1: Hold
IB-1501279-H
#1 Slot No.
#1 Network Type
#1 Network No.
#1 Total Stations
#1 Station No.
#1 Mode
#1 DLink Fault St.
714
Selection of parameter application slot
Network type
Network No.
Total number of slave stations
Station No. (local station)
Communication mode
Data link error station setting