Equipment Removal

Remove Fan Unit

9.4
Remove Fan Unit
The following links lead to related information:
Install Fan Unit
Warning: Fan units are required to provide sufficient airflow (heat removal) through the blade. If a Fan
unit is removed, reinstalled, or replaced, reinsert the Fan unit within 3 minutes; otherwise, the blade and
service PIUs could be damaged because of overheating. The operating temperature is 5...40 °C.
Warning: PIUs can be damaged by ESD during installation or removal or whenever they are contacted.
Wear an ESD wrist strap with a minimum resistance of 1 megohm that is properly secured to the ESD
grounding wrist strap connection post to prevent possible PIU damage. Before using the strap, check it for
opens, shorts, and the minimum resistance value. If the strap does not pass these checks, do not use it.
Step 1
Locate the Fan unit to be removed.
Note: If the Fan unit is being replaced because of a failure, FAN LEDs on rear-left side of the blade can identify
which Fan unit has failed.
INPUT RATING:
-48V ---.
20A MAX.
FUSED AT 25A
Maintenance Ports
(Factory use only: do not use.)
Figure 170
FAN LEDs
·
Release 19.1.1
Issue 1.1, May 2021
Electrostatic Discharge (ESD)
Wrist Strap Grounding Post
FAN LEDs
430
Fujitsu and Fujitsu Customer Use Only