Huawei SmartAX MA5603T Configuration Manual page 124

Access module
Hide thumbs Also See for SmartAX MA5603T:
Table of Contents

Advertisement

SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
Item
Battery
management
parameters
The upper/
lower
temperature
alarm limits
or the upper/
lower
temperature
test limits
Battery set
power-off
parameters
Power
distribution
parameters
Battery
discharging
test
parameters
Power
rectifier
module
parameters
Issue 01 (2014-04-30)
Data Plan for the F01D500
Cabinet
Current-limiting coefficient for
battery charging: 0.15
Interval of battery equalized
charging: 60 days
Number of battery sets: 1
Capacity of the battery set: 150 AH
The battery capacity is configured
according to the actual value. the
F01D500 cabinet uses the 2 * 75
AH or 2 * 92 AH batteries.
Upper temperature threshold of the
battery set: 80°C
Lower temperature threshold of the
battery set: -20°C
Temperature compensation
coefficient of the battery set: 80
mV
Battery set power-off permission
status: permit
Battery set power-off voltage: 43 V
AC overvoltage alarm threshold of
the power supply: 280 V
AC undervoltage alarm threshold
of the power supply: 180 V
DC overvoltage alarm threshold of
the power supply: 58 V
DC undervoltage alarm threshold
of the power supply: 45 V
Battery auto-discharging test: auto-
test
Battery set auto-discharging test
permission status: permit
Battery auto-discharging test
period: 60d
The number of the power rectifier
modules: 0
The number of the power rectifier
modules is configured according to
the actual value. EPS75-4815AF
supports up to 5 rectifier modules.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1 Commissioning
Data Plan for the N66 Cabinet
Current-limiting coefficient for battery
charging: 0.15
Interval of battery equalized charging:
60 days
Number of battery sets: 1
The battery capacity is configured
according to the actual value.
Upper temperature threshold of the
battery set: 80°C
Lower temperature threshold of the
battery set: -20°C
Temperature compensation coefficient
of the battery set: 80 mV
Battery set power-off permission
status: permit
Battery set power-off voltage: 43 V
AC overvoltage alarm threshold of the
power supply: 280 V
AC undervoltage alarm threshold of the
power supply: 180 V
DC overvoltage alarm threshold of the
power supply: 58 V
DC undervoltage alarm threshold of the
power supply: 45 V
Battery auto-discharging test: auto-test
Battery set auto-discharging test
permission status: permit
Battery auto-discharging test period:
60d
The number of the power rectifier
modules: 0
The number of the power rectifier
modules is configured according to the
actual value. EPS75-4815AF supports
up to 5 rectifier modules.
99

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartax ma5600tSmartax ma5608t