SmartAX MA5600T/MA5603T/MA5608T Multi-service
Access Module
Commissioning and Configuration Guide
name Smoke digital-alarm 15
huawei(config-if-power4845-0)#power outside-digital 5 available-level low-level
name HEX digital-alarm 13
huawei(config-if-power4845-0)#power outside-digital 6 available-level low-level
name MDF-door digital-alarm 9
huawei(config-if-power4845-0)#display power system parameter
huawei(config-if-power4845-0)#display power environment parameter
huawei(config-if-power4845-0)#display power alarm
huawei(config-if-power4845-0)#quit
huawei(config)#save
1.3.16.7 Configuring the Environment Monitoring Parameters of the ETP4830
This topic describes how to configure the environment monitoring parameters of the ETP4830
through the CLI.
Mapping Between Monitoring Parameters and Device Ports
The ETP4830 monitoring scheme can be used in the F01S300 cabinet.
mapping between the monitoring parameters displayed
NOTE
Table 1-34 Mapping between the monitoring parameters displayed on the host and the ports on
the sensor transfer box
Monitoring
Parameter
Displayed on
the Host
Digital 0
Digital 1
Digital 2
Digital 3
Digital 4
Digital 5
Digital 6
Door alarm
Wiring alarm
Battery Tem
Issue 01 (2014-04-30)
Before adding a user-defined analog or monitoring digital parameter, make sure that the port corresponding
to this parameter is properly connected to an environment monitoring cable.
Device Port
JTD1
JTD2
JTD3
JTD4
JTD5
JTD6
JTD7
JTM1
JTP1
VBTEM2
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Application in the F01S300 Cabinet
Not connected by default, used to add a user-defined
monitoring digital parameter
Battery compartment heater (optional
configuration)
Device compartment heater (optional
configuration)
Surge protector
Not connected by default, used to add a user-defined
monitoring digital parameter
Heat exchanger
Door status sensor of the MDF compartment
Door status sensors of the device compartment and
heat exchanger compartment
MDF
Battery temperature sensor
1 Commissioning
Table 1-34
describes the
109