2 Installation and Commissioning, IRC5
2.5.10. The MOTORS ON/MOTORS OFF circuit
Continued
Technical data
ES1 and ES2 max output voltage
ES1 and ES2 max output current
External supply of ES relay
Rated current per chain
Max. potential in relation to the cabinet earthing
and other signal groups.
Signal class
Connection to operating mode selector (Option)
The illustration below shows the connection of terminals for customer use.
xx0500002092
A
External manual FS (Full Speed) 100% is an option.
Technical data
Max. voltage
Max. current
Max. potential in relation to the cabinet earthing
and other signal groups.
Signal class
72
Mode selector
120 VAC or 48 VDC
120 VAC: 4 A
48 VDC L/R: 50 mA
24 VDC L/R: 2 A
24 VDC R load: 8 A
24 VDC ± 10% between ter- minals X1:9,
8 and X2:9, 8 respectively.
Note! In case of interference, the
external supply must be properly filtered.
40 mA
300 V
Control signals
48 VDC
4 A
300 V
Control signals
3HAC021313-001 Revision: K